Flagship Data Centers

We have six data centers across the US and Europe, with flagship locations in New Jersey and Amsterdam.

USA

United States

North Bergen, NJ

Power Systems

Power Density

  • 200 Watts Per Sq. Ft.

UPS System

  • Eight parallel UPS systems configured N+1
  • Primary UPS systems provide 13568 kW
  • UPS System deployed to carry full design load 12 --- 15 minutes
  • 17,638 kW of UPS sub-distribution infrastructure

DC Plant

  • Six redundant DC plant systems
  • Each DC System is deployed as A & B plants design classification as 2N
  • Primary DC power systems provide 691 kW
  • 1037 kW of matching DC sub-distribution infrastructure
  • DC Plant systems are deployed to carry full load for 4 hours via dedicated battery banks per DC plant
  • -48 Volt DC Battery Plant
  • 2400 amp expandable to 10,000 amp
  • 2-hour battery reserve non-redundant, 4 hours redundant
  • ‘‘True’’ A/B Power feeds

Standby Generator

  • 2000 kW generators configured in N
  • 24 hours of continuous generator run time at full design load
  • Generator systems both auto start and auto transfer

Environmental Controls

Fire Supression

  • Pre-Action double interlock fire suppression system
  • Dual zoned smoke and heat fire alarm detection system

HVAC

  • 14259 KW of Heat Rejection Capacity
  • Interior and exterior systems are each deployed at N + 1
  • A/C units maintain a climate of 72 degrees (+/- 5) and 30-60% humidity (SLA Statement)

Alarm Monitoring

  • All essential equipment is tied into Falcon Alarm System (UPS, DC plant, PMMs, BDCBBs, ATS’s, Generators, Diesel tanks, TVSS, Fire System)
  • Operations Alarm Management (OAM) Group monitors facility falcon units 24/7/365
  • Alarming is a dry contact system set to normally closed

Security

  • Card access control at all secure areas/doors
  • Surveillance cameras at strategic locations, exterior and interior CCTV coverage
  • Fully fenced and secure perimeter
  • 24/7 On-site security personnel
  • 24/7 Corporate security surveillance
  • Speaker and Phone Systems installed throughout facility for correspondence with local and remote
  • security personnel
  • 30 days of on-site video back-up
EU

Europe

Amsterdam, NL

Power Systems

  • primary HV power provision
  • LV switchboards for power provision to the room
  • 800 watts/sq m
  • on site sub-stations
  • standby generators with a minimum 24 hours autonomy at full capacity
  • Uninterruptible Power Supplies (UPS)
  • sufficient fuel on site to run for days, together with priority re-fuelling contracts
  • planned preventative maintenance programs
  • process oriented engineers and on site controllers available 24x7

Environmental Controls

HVAC

  • Room Air Conditioning Units (RACU's)
  • regulated humidity controls
  • chilled water HVAC system with no environmentally hazardous refrigerants
  • adjustable floor grills to achieve balanced air flows
  • planned preventative maintenance and 24x7 on-site engineers

Fire Protection

  • VESDA (Very Early Smoke Detection Apparatus) systems
  • environmentally-friendly gas suppression systems using Argonite or Inergen
  • gas and smoke extraction in conjunction with pressure relief systems
  • fire alarms and wet-pipe sprinkler systems in ancillary areas
  • fire detection and suppression systems linked to BMS
  • on-site 24x7 monitoring

Security

  • door access controls at main site and building entrances
  • proximity activation cards to authorize access levels
  • movement logs on all proximity card usage
  • internal and external CCTV cameras and digital image archiving
  • internal and external intruder detection devices
  • vehicle entrance barriers and secure loading bays
  • strict policies on handling customers’ postal packages
  • security systems linked to central BMS
  • 24x7 monitoring by dedicated security teams